Temperature Control System Solution Provider - Shanghai Yuexi Trade Development Co., Ltd

Shanghai Yuexi Trade Development Co., Ltd

Phone:(+86)189 1548 0537

Phone

(+86)189 1548 0537
PAC30A-B160S series new three-phase power regulator
◆ Adjustable power/voltage can be set
◆ Manual/automatic control
◆ Suitable for resistive loads
◆ Automatic+external voltage limit control
◆ Grounding/ungrounded load center can be set
◆ Special working voltage and frequency can be customized
◆ External switch controls start/stop
◆ CE certification
Product Details
Technical Specifications
Product Model
Product size


Shanghai Yuexi Trade Development Co., Ltd. power regulator design concept

1、Design of the Control Board

PAC30A series: the use of digital circuit intelligent design, automatic phase discrimination, and strive for simple wiring and high quality requirements, low-cost design, basically achieve the cost of the solid state relay, while making up for the defects of the solid state relay, so that the function of PAC30A has reached: power regulation/voltage regulation arbitrary setting, initial power-on with slow start, manual/automatic adjustment output, output limit, load center grounding or non-grounding arbitrary setting, special voltage and frequency optional, etc.

2、Selection of radiator

The radiator adopts a blade radiator with high heat dissipation performance. 

3、Selection of fans 

120 axial fan, ball bearing type. It has the characteristics of long life and low heat generation.

4. Selection of thyristor modules

 2 types of thyristor modules are used:

 A: The Ximenkang module imported from Germany is characterized by low heat generation and high reliability. 

 B: Domestic module, specially selected low-voltage drop chip, soldered and pressed with imported insulating materials with high heat dissipation performance Joined. It is characterized by strong overload capacity and reliable quality.



1 Load Control Element
hyristor (SCR) Module
2 Load Power Supply
Three-phase 380V AC ±10% 50HZ
3 Current Capacity
25A, 50A, 60A, 80A, 90A, 115A, 140A, 160A, 190A, 250A, 320A, 400A AC
4 Control Board Power Supply and Power Consumption

Power Supply: 380V AC ±10% 50HZ, requires same phase as load power supply

Power Consumption: 5W maximum

5

Fan Power Supply

(depending on model)

Voltage: 220V AC  Current: Below 0.5 A
6 Control Input
4~20mA or 0-10V DC input, receiving impedance 100Ω
7 LED Status Indicator  

Input Indicator LED (1): Red 

Three-color Status LED (1): Green, Running (output on) 

                   Yellow flashing, Stopped (no output) 

  Red-green flashing, Heat sink overtemperature alarm (no output)

8 Control Mode

Phase Control: Continuous voltage regulation        

Power Control: Resistive cycle zero-crossing power regulation

9 Output Resolution
Phase Control: 0.2°, Power Control: 20ms
10 Phase Shift Range

0~175°, Star load (center point grounded) 

0~150°, Delta load or Star load (center point ungrounded)

11 Drive Output

With single silicon anti-parallel thyristor module Variable width pulse: 8°~120°  

Voltage: 5V   Current: 100mA maximum

12 Manual Mode
External 10KΩ potentiometer adjustment
13 Soft Start Time
During phase control, adjusted by P3 potentiometer. Adjustment range: 0.2~120 seconds
14 Soft Shutdown Time
During phase control, fixed at 10 seconds
15 Voltage Limit

Adjusted by onboard P1 potentiometer or external 10KΩ potentiometer.

Adjustment range: 0~100%

16 Heat Sink Overtemperature Protection
80℃ temperature switch, normally closed contact Action time: < 20ms
17 Alarm Output

Activated when heat sink overtemperature 

Specification: 1 normally open contact, 1A 250V AC resistive

Output terminals: CN2-1, CN2-2

18 Emergency Stop

When the alarm is activated, the control output will stop urgently 

Action time: < 20ms 

Disable: After the alarm is dismissed, enter the standby state or power on again

19 Fan Control

The fan is connected to a normally open temperature switch at 40°C. When the

heatsink temperature is below 40°C, the fan does not rotate, ensuring the fan's lifespan. 

Fan power supply: 220V.

20 Start/Stop Switch (External Switch)

R1 terminal: CN1-3 terminal, RS terminal: CN1-7 terminal.

R1 - RS terminal: Voltage-free contact input.

Short-circuit voltage regulation (factory setting): slow shutdown, open circuit: slow start

21

Power regulation/voltage regulation switching

 (SW1-1 DIP Switch)

SW1-1=ON, Voltage Regulation (Factory Setting)
SW1-1=OFF, frequency power regulation
22 Working environment
and storage temperature
Temperature range: 0~+40°C
H
umidity range: 90% Rmax, ncondensation
Altitude: below 2000m
Storage temperature: -10~+60°C

Other requirements: good ventilation, ndirect sunlight othermal radiation, no

corrosion sexual, flammable gases

23 Installation form and requirements
Wall-mounted, vertically mounted, well ventilated
24 Insulation Insulationresistance
Dielectric strength
Insulation resistance: module output and housing, 500VDC 20MΩ minimum

The power supply end and enclosure of the control board are 500VDC 20MΩ minimum
Control input and housing, 500VDC 20MΩ minimum
The input and power supply othe control board are 500VDC 20MΩ minimum
Dielectric Strength: 2000VAC for 1 minute between module output and housing

Between the control power supply and the housing, 2000VAC for 1 minute


Classic SCR three-phase power regulator selection table


Code  
Basic parameters
    PAC30A-     

Input signal: 4-20mA DC signal (input impedance 120 ohms), output form phase shift voltage regulation/frequencyower regulation can be set arbitrarily,power on slow start 0-60 seconds 

can be set, radiator over-temperature alarm protection, manual automatic non-disturbance switching. It is suitable for Y-type load center connection or dangling, triangular load. Load power supply 380VAC ± 10%, 50Hz

The default input signal is 4-20 mA, and the 0-5V and 0-10V input require remarks The default power supply of the fan is 380V pass-through, and 220V control is required.

    Radiator unit   
Overall dimensions of the whole machine
SCR specifications

Load power

 (resistive)

B160S-: 1 fan, blow-type forced air cooling. Radiator capacity: ambient temperature at 40 degrees: 150A/phase. Natural heat dissipation conditions: 15A/phase.
L 290mm, W 170mm, D 240mm, 4 hole mounting
Mounting hole spacing:100mm*274mm, 
hole diameter 10mm
MKKT90A
42KW
MKKT110A
52KW
MKKT130A
63KW
MKKT180A
90KW
MKKT200A
98KW


unit mm A B C D E
B160S 290 171 240 100 274